Prefabricated fire extinguishing devices set in the protection zone shall be started by automatic control and manual control. In the automatic control program, delay injection with adjustable time of 0 ~ 30s should be arranged. The delay time should be set according to the need for people to evacuate from the protection zone as soon as possible; For the protection zone where no one works at ordinary times, it can be set as 0s. In the protection area where the designed concentration of fire fighting is more than 9%, a switching device between manual and automatic control should be added to switch the fire fighting system to the manual control position when someone enters the protection area; When people leave, return to the automatic control position.
Specification | Technical parameter |
Working pressure | 4.2Mpa |
Type | Fm200 direct type |
Max working pressure | 5.2Mpa |
model | QMQ4.2/100N |
Working temperature | 0-50℃ |
Density of unit volume | ≤950kg/m³ |
Max length of detecting tube | 50m |
Quantity of agent | 100kg |
We can supply different kinds of Automatic Fire Extinguisher below:
FM200 Heptafluoropropane(HFC-227ea) Fire Extinguisher: FM200 Automatical Cabinet Fire Extinguisher System;
If you have questions or requirements,donnot hesitate to let us know,we will supply best service to you in the first time,Including best Program and design for you to save your cost and make it most effective.
We hope our Ding Ya Brand Fire Extinguisher System will be your Important choise.
Thank you very much for your best cooperation and support!
The door
Feature:
1.Fire Equipment is our TOP products.We are most Professional Fire Extinguisher Manafuturer,located in Guangzhou,China.
We can supply different kinds of Automatic Fire Extinguisher below:
FM200 Heptafluoropropane(HFC-227ea) Fire Extinguisher: FM200 Automatical Cabinet Fire Extinguisher System;
If you have questions or requirements,donnot hesitate to let us know,we will supply best service to you in the first time,Including best Program and design for you to save your cost and make it most effective.
We hope our Ding Ya Brand Fire Extinguisher System will be your Important choise.
Thank you very much for your best cooperation and support!
products
Application
The pipe network type fm200 fire suppression system is suitable for a lot of places and several kinds of fires. The followings are some examples for customer as reference:
- Telecommunications and data processing
- Switch gear rooms
- Military applications and cell sites
- High-tech medical application
- Computer rooms
- Telecommunication centers
- Records and data archives
- Testing/imaging equipment
- Reference material
- Chemical laboratories
Feature:
1.Fire Equipment Vaporized completely in the atmosphere without residue and pollution.
2.Colorless,Odorless,non-conductive,insulation,lowest toxicity
3.Beautiful apperance,fashion design and reliable performance.
4.Application:Computer room,Switching Room,Precision Instrument Room,Hospital,TV Station,Railway Station,Museum,Institution,Laboratory,Library,Data Room,Power Factory,Archives etc.
Enterprise production base
AArticle 7.0.3 Automatic control device shall be started after receiving two independent fire signals. The manual control device and the manual-to-automatic switching device shall be located outside the exit of the evacuation exit of the protection zone, which is convenient for operation. The mechanical emergency operation device shall be located in the bottle storage room or outside the evacuation exit door of the protection area, which is convenient for operation; Moreover, its operation mode should be completed in two steps. Article 7.0.4 The operation and control of fire extinguishing system and prefabricated fire extinguishing device shall include the operation and control of equipment such as opening closing device, ventilator and fire damper which need linkage. In places with fire control centers, the action information of fire control systems in each protection area shall be transmitted to the fire control centers. This information includes fire information capture and extinguishing action, manual and automatic conversion, system failure, etc.